rtek Ventier PR 60 with rotary heat exchanger
Ready-to-use air handling unit with side connection
Specifications
Properties
Installation
Applications
Documents
Specifications
- fully assembled, ready-to-use air handling unit
- rotary heat exchanger
- airflow range 3 – 6,28 m³/s
- also available as a 4-section module-model
- dimensions 4270x2560x2970 mm (WxDxH) (width does not include electric heater or electrical center)
- dimensions of the module-model 4480x2560x2970 mm (WxDxH) (width does not include electric heater or electrical center)
- weight 2500 kg
- duct connections: supply and extract air 2100×1000 mm, outdoor and exhaust air 1900×900 mm (exhaust air also available at the top)
- EC-fans
- heating with water or electricity
- return-air section (optional)
- automation
- Building Management System
- Fidelix FxVent
- Ouman Ouflex A
- Siemens Climatix
- unit handedness selectable
Precise dimensions and technical documents can be found in the PAMON DESIGNER
Cooling options
- liquid cooling coil (JP)
- direct evaporation coil (DX)
Properties
- electrical and control center, as well as shunt kit already installed
- effective filtration and sound insulation
- user and maintenance friendly design, all functions pre-tested at the factory
- also available as a module-model
Installation
- delivered fully assembled (excluding module-models)
- minimum size of opening for hauling 2595×3000 mm (assembled)
- minimum size of opening for hauling for module-model 1155×3000 mm (disassembled)
- maintenance space requirement 4770×2500 mm
- maintenance space requirement for module-model 4980×2500 mm
- quick and easy to install
- factory tested unit with ready to connect automation and electric connections
- everything is ready, just connect the power supply, duct system, heating pipes and condensate removal
Applications
- offices
- small industrial facilities
- commercial premises
- kindergartens
- schools, distributed demand-driven ventilation
- nursing homes
- restaurants
Documents
Technical brochure
rtek Ventier PR 60
Operating and Maintenance Instructions
Ventier operating and maintenance instructions
Installation Instructions
Installation Instructions PR 60 -L (coming soon)