NB! The dimensions of the unit have been reduced 3/2025
rtek Ventier PR 40 with rotary heat exchanger
Ready-to-use air handling unit with side connection
Specifications
Properties
Installation
Applications
Documents
Specifications
- fully assembled, ready-to-use air handling unit
- rotary heat exchanger
- airflow range 2 – 4,23 m³/s
- also available as a 3-section module-model
- dimensions 2680x2110x2400 mm (WxDxH) (width does not include electric heater or electrical center)
- dimensions of the module-model 2820x2110x2400 mm (WxDxH) (width does not include electric heater or electrical center)
- weight 1800 kg
- duct connections: supply and extract air 1900×900 mm, outdoor and exhaust air 1600×900 / Ø 800 mm (exhaust air also available at the top)
- EC-fans
- heating with water or electricity, in unit’s duct output
- return-air section (optional, increases the unit’s width by +870 mm, module-model +940 mm)
- automation
- Building Management System
- Fidelix FxVent (no return-air function)
- Ouman Ouflex A
- Siemens Climatix
Precise dimensions and technical documents can be found in the PAMON DESIGNER (update coming soon with new dimensions)
Cooling options
- liquid cooling coil (JP), in unit’s duct output
- direct evaporation coil (DX), in unit’s duct output
Properties
- electrical and control center, as well as shunt kit already installed
- effective filtration and sound insulation
- user and maintenance friendly design, all functions pre-tested at the factory
- also available as a module-model
Installation
- delivered fully assembled (excluding module-models)
- minimum size of opening for hauling 2145×2430 mm (assembled)
- minimum size of opening for hauling for module-model 975×2430 mm (disassembled)
- maintenance space requirement 3680×2000 mm (not including cooling coil)
- maintenance space requirement for module-model 3820×2000 mm (not including cooling coil)
- quick and easy to install
- factory tested unit with ready to connect automation and electric connections
- everything is ready, just connect the power supply, duct system, heating pipes and condensate removal
Applications
- offices
- small industrial facilities
- commercial premises
- kindergartens
- schools, distributed demand-driven ventilation
- nursing homes
- restaurants
Documents
Technical brochure
rtek Ventier PR 40
Operating and Maintenance Instructions
Ventier operating and maintenance instructions
Installation instructions
Installation instructions PR 40 -L
Installation instructions PR 40 -R